Medium-Temperature Self-Regulating Heating Cable SRS
Freezing protection of all components of roofs and drainage systems;
Maintenance of the process temperature of pipelines and tanks in an explosion-hazard area.
Versorgungsspannung :
220V-240VNennleistung :
15W/m, 30W/m, 45W/m, 60W/mMaximale Temperatur im stromlosen Zustand :
200°CMaximale Energietemperatur :
120°CMinimale Installationstemperatur :
-40°CTSelf Regulating Heat Cable Specification:
Supply voltage: 220V to 240V
Max. permissible operating temperature under load: +120 °C
Max. permissible operating no-load temperature: +200 °C
Temperature class: T4, T3
Protection rating: IP66
Minimum installation temperature: -40 °C
Minimum bending radius: 25 mm at -40 °C
Rated power: 10 ,16, 24, 30, 40 (W/m) at 10°C
Explosion-protection type: 1ExellCT3.....T6GbX
Self Regulating Heat Cable SRS Design:
1. 19*0.32 Nickel plated copper wire
2. Self-regulating conductive core
3. Thermoplastic insulation
4. Tinned copper braid
5. Fluoroplymer outer jacket
Technical Data:
Technical Data | 15SRS2CF | 30SRS2CF | 45SRS2CF | 60SRS2CF |
Output Power@+10°C(W/m) | 15 | 30 | 45 | 60 |
Maximum Energized | 120°C | 120°C | 120°C | 120°C |
Maximum Un-energized | 200°C | 200°C | 200°C | 200°C |
Maxlength@0°C | 70/102/- | 60/78/- | 54/65/- | 42/66/76- |
Max length@-20°C 16/20A(m) | 78/94/- | 60/90/- | 46/67/75 | 36/52/62 |
Size (mm) | 10.1*5.1 | 10.1*5.1 | 10.1*5.1 | 10.1*5.1 |
Weight((kg/km) | 98 | 98 | 98 | 98 |
Self Regulating Heat Cable SRS Features:
• Automatic regulation of heat release when the temperature of the heated surface changes.
• It can be cut of to the required length.
• It does not overheat or burn through in case of self-crossing.
• It can be used in both safe and explosion-hazard areas
Area of Use
Unsere Stunden
Mo. 21.11. - Mi. 23.11.: 9.00 - 20.00 Uhr
Do. 24.11.: geschlossen – Happy Thanksgiving!
Fr. 25.11.: 8:00 - 22:00 Uhr
Sa. 26.11. - So. 27.11.: 10.00 - 21.00 Uhr
(Alle Stunden sind Eastern Time)